Code: C6400
Description: Zero-crossing signal problem
• The main PCB does not detect the zero-crossing signal (Z CROSS SIG) for the time specified below. At power-on: 5 s Others: 5 s
• The main PCB does not detect the zero-crossing signal (Z CROSS SIG) for the time specified below. At power-on: 5 s Others: 5 s
Causes: Poor contact in the connector terminals. Defective power source PCB. Defective main PCB.
Remedy: Check the connection of connectors YC1-3 on the main PCB and YC2-6 on the power source PCB, and the continuity across the connector terminals. Repair or replace if necessary. Check if the zero-crossing signal is output from YC2-6 on the power source PCB. If not, replace the power source PCB. Replace the main PCB if C6400 is detected while YC2-6 on the power source PCB outputs the zero-crossing signal.